Enter the calc summary from your hydraulic calculations and get the two signs NFPA 13 wants hanging at the riser — the hydraulic design information sign and the general information sign — clean, printable, and under your company's name.
This heads both signs. The signs carry your company's name, not ours.
One card per design area, from your hydraulic calculations. NFPA 13 (2022) §29.4.3 requires each of these items on the sign: location of the design area, its size (area or number of sprinklers), the discharge density, the required flow and residual pressure at the base of the riser, the occupancy/commodity classification with maximum storage height and configuration, the hose stream allowance, and the installing contractor's name.
NFPA 13 (2022), Table 19.2.3.1.1 (density & design area, normal case) and Table 19.2.3.1.2 (hose stream allowance & duration). Tap a row to fill the first design area — or use the hazard buttons on each card. These are the standard occupancy-hazard points; storage and special occupancies use their own chapters, and the edition your AHJ adopted is the final word.
| Hazard class | Density (gpm/ft²) | Design area (ft²) | Hose allowance (gpm) | Duration |
|---|---|---|---|---|
| Light Hazard | 0.10 | 1,500 | 100 | 30 min |
| Ordinary Hazard Group 1 | 0.15 | 1,500 | 250 | 60–90 min |
| Ordinary Hazard Group 2 | 0.20 | 1,500 | 250 | 60–90 min |
| Extra Hazard Group 1 | 0.30 | 2,500 | 500 | 90–120 min |
| Extra Hazard Group 2 | 0.40 | 2,500 | 500 | 90–120 min |
Total system demand is the governing design area's sprinkler demand plus the hose stream allowance. The flow and pressure you enter at the base of the riser should match it — if they don't, the check below flags it before you print.
NFPA 13 (2022) §29.6.2 lists up to 20 items. Check the ones that apply to this system and fill them in — only checked items print on the sign. Items 1–3 and 17 pull from what you already entered above; edit them here if the sign needs different wording. §29.6.3 allows this sign and the hydraulic sign to be combined into one — this tool prints them as two plates, which also satisfies the requirement.
One free email every week — what changed in fire protection this week, in five minutes.
Why this is free
This tool is free, and it stays free. We build these because RiserRoom's whole job is to give the fire sprinkler industry as much value as we can. The newsletter is the same idea in your inbox: five minutes a week on the stuff that hits your bids, your backlog, and your bottom line.
Subscribe freeMore free tools at riserroom.com/tools