NFPA 25 Quick-Reference Card

Sprinkler inspection, testing & maintenance frequencies — the ones shops actually look up. One page, for the truck or the riser room wall.

NFPA 25 — Sprinkler System ITM Frequencies

NFPA 25 (2023 edition), Tables 5.1.1.2 & 13.1.1.2 — the standard's own frequency tables, with section references. Quick reference only: it is not the standard. The edition your AHJ adopted — and local amendments — govern.

I = inspect  ·  T = test  ·  M = maintain. Frequencies are the maximum interval between visits — sooner is always allowed, and the AHJ or insurer can require more.

Weekly

Control valvesIAll valves except locked or supervised — verify open13.3.2.1
Backflow preventerIReduced-pressure assemblies & detectors13.7.1
Master PRVIMaster pressure-regulating valve13.5.4.1
Deluge enclosureIValve enclosure, during cold weather — daily/weeklyCh. 4

Monthly

Control valvesILocked or supervised valves13.3.2.1.1
Gauges — wetIOperable, not physically damaged13.2.4.1.1
Gauges — dry / preactionIAir / nitrogen pressure maintained13.2.4.1.3
Dry / preaction / deluge valveIValve exterior13.4.5.1.2 / .3.1.1 / .4.1.1
Air supplyIAir compressors & nitrogen generators13.10.2

Quarterly

Control valvesIElectrically supervised valves13.3.2.1.2
Valve supervisoryISupervisory signal initiating device13.3.2.1.3
Waterflow alarmsIAlarm devices13.2.3
Supervisory devicesIExcept valve supervisory switches13.2.5.1
Alarm valveIExterior condition13.4.1.1
Fire dept. connectionIAccessible, caps in place, no damage13.8.1
Hose valvesIStandpipe hose valves13.6.1
Gauges — water pressureINormal water supply pressure maintained13.2.4.1.2
Dry pipe — priming waterTPriming water level13.4.5.2.1
Dry pipe — quick-openingTQuick-opening device13.4.5.2.4
Preaction — priming / airTPriming water; low air pressure alarms13.4.3.2.1 / 13.4.3.2.11
Main drainTQuarterly where the sole supply passes through a backflow preventer or PRV — otherwise annually13.2.2

Semiannual

Waterflow alarmsTFlow the inspector's test connection; alarm must sound13.2.3
Control valve supervisoryTSupervisory signal test13.3.3.5

Annual

SprinklersICondition, orientation, clearance, corrosion, paint, loading — incl. guards5.2.1 / 5.2.1.1.7
Spare sprinklersIStock on hand, correct types & temperatures5.2.1.4
Pipe & fittingsICondition, hangers, seismic bracing5.2.2 / 5.2.3
Hydraulic signIHydraulic design information sign — legible, in place5.2.5
Information signsIGeneral information sign & related signage5.2.7–5.2.9
Dry pipe valveIInterior13.4.5.1.3
Dry pipe alarmsI/TLow-temp alarm (I); low air pressure alarm testCh. 4 / 13.4.5.2.6
Preaction valveIInterior — annually / 5 years13.4.3.1.2
Preaction — low temp alarmTLow-temperature alarm test13.4.3.2.12
Control valvesTOperation & position — full close and reopen13.3.3.1
Main drainTAt each water supply riser; record static & residual13.2.2
Dry pipe trip testTTrip test (full-flow every 3 years)13.4.5.2.2
Backflow assembliesTFull test13.7.2
Supervisory devicesTExcept valve supervisory switches13.2.5.2
Antifreeze solutionTConcentration / specific gravity check5.3.4
OS&Y valvesMControl valve maintenance13.3.4
Dry pipe valveMValve maintenance13.4.5.3
Preaction / deluge valvesMValve maintenance — annually / 5 years13.4.3.3 / 13.4.4.3
Cooking protectionMSprinklers / nozzles over commercial cooking equipment5.4.1.8

Every 3 years

Dry pipe full-flow tripTFull-flow trip test13.4.5.2.2.2
Dry pipe air leakageTSystem air leakage test13.4.5.2.9
Preaction air leakageTSystem air leakage test13.4.3.2.6
Deluge / preaction tripTFull-flow trip test every 3 years (annual trip test between)13.4.4.2.3 / 13.4.3.2.2

Every 5 years

Internal pipingIInternal assessment — obstruction, corrosion, debrisCh. 14
Alarm valveIInterior; strainers, filters, orifices13.4.1.2
Check valveIInterior13.4.2.1
Backflow preventerIInterior13.7.1.3
Dry / preaction / deluge strainersIStrainers, filters, orifices13.4.5.1.4 / .3.1.3 / .4.1.3
GaugesTReplace, or test against a calibrated gauge13.2.4.2
Extra-high-temp sprinklersTSample-test or replace5.3.1
Harsh-environment sprinklersTSample-test or replace5.3.1

Sprinkler sample testing — by age in service

Standard-responseTAt 50 years, then every 10 years; at 75 years, every 5 years5.3.1
Fast-responseTAt 25 years, then every 10 years (except ESFR / CMSA)5.3.1
ESFR / CMSATAt 20 years, then every 10 years5.3.1
Dry sprinklersTAt 20 years, then every 10 years5.3.1

Scope: sprinkler systems and their common components (Chapter 5 & Chapter 13 valves). Fire pumps, standpipes, hydrants, tanks, and foam/mist systems have their own chapters and their own tables — they are not on this card.

Editions move: frequencies and section numbers change between NFPA 25 editions (the 2023 edition is used here; the 2026 edition is now published). A frequency on this card is only right if it matches the edition your AHJ adopted. When in doubt, open the standard — NFPA offers free read-only access at nfpa.org.

Gauges, read carefully: wet-system gauges get a monthly condition check (§13.2.4.1.1) and a quarterly water-pressure check (§13.2.4.1.2). Dry/preaction air gauges are monthly — quarterly only where air-pressure supervision reports to a constantly attended location (§13.2.4.1.3.2). Older editions said weekly for dry-system gauges; the 2023 text above is what this card follows.

A free resource from RiserRoom — the weekly fire protection newsletter. riserroom.com