Sprinkler Spacing & Coverage Quick Check

Room size plus hazard class, and you get the NFPA 13 limits for standard spray sprinklers, a suggested regular grid, and a pass/fail check of a layout you already have in mind. A check, not a design.

Room & hazard

Standard spray pendent or upright sprinklers, smooth unobstructed ceiling. If the ceiling is obstructed, beamed, or sloped — or the heads are extended coverage, sidewall, CMSA, or ESFR — the tables below do not apply directly; use the head's listing and the NFPA 13 chapter for that head type.

Just checking the math? Load the worked example (40 × 30 ft, OH2 → 12 heads on a 10 × 10 ft grid, 100 ft² per head).

The limits for this hazard

NFPA 13 (2022), Table 10.2.4.2.1 — protection area and maximum spacing of standard pendent and upright spray sprinklers; minimum spacing §10.2.6.4.1; distance to walls §10.2.6.2.1 (max one-half the spacing) and §10.2.6.3 (min 4 in.). A listed head's spacing may be more restrictive than the table — the listing wins.

Hazard classMax coverage / headMax spacingMin spacingMax from wall
Light Hazard225 ft²15 ft6 ft7.5 ft
Ordinary Hazard 1130 ft²15 ft6 ft7.5 ft
Ordinary Hazard 2130 ft²15 ft6 ft7.5 ft
Extra Hazard, density < 0.25130 ft²15 ft6 ft7.5 ft
Extra Hazard, density ≥ 0.25100 ft²12 ft6 ft6 ft

Suggested regular grid

The fewest heads on an even grid that satisfies both the spacing limit and the coverage limit. A starting point for a layout — not the layout. Real rooms have doors, beams, lights, and obstructions that move heads around.

Suggested heads for this room
—

Check my layout

Already have a spacing in mind? Enter it and get a pass/fail against the same table. Wall distance is measured from the head to the wall — for an even grid it is half the spacing, but enter the real number if the end heads are offset.

What this does not check: obstructions and the 18 in. clearance below sprinklers, ceiling height and slope, deflector distance below the ceiling (1–12 in. for standard spray under unobstructed construction, §10.2.7.1.1.1), beams and joists, the small-room rule (up to 9 ft from a single wall, §10.2.5.2.1), or the hydraulic design — density, remote area, and flow still come from your calc. Extended coverage, sidewall, CMSA, ESFR, and residential heads each have their own spacing tables. When the table and the head's listing disagree, the listing governs.